Case Details

Status:

REFERRED

Type:

RES: MINIMUM HOUSING

Entered Date:

04/16/2003

Applicant:

MITCHELL LARRY W

Description:

COMPLAINT:MIN HOUSING-PLUMBING SYSTEMS IN DWELLING-ALL SYSTEMS MUST BE MAINTAINED IN GOOD REPAIR; MUST HAVE ADEQUATE POTABLE WATER SUPPLY;EVERY FIXTURE & WASTEPIPE & GAS CONNECTION MUST BE IN GOOD REPAIR & FREE FROM OBSTRUCTIONS. ELECTRICAL SYSTEM IN DWELLING-ELECTRICAL FACILITIES MUST BE MAINTAINED FREE OF HAZARDS SUCH AS IMPROPER WIRING, EXPOSED WIRING, OVERLOADED CIRCUITS, IMPROPER USE OF EXTENSION CORDS. ACCESS CONTROL-EXTERIOR DOORS & WINDOWS MUST HAVE OPERABLE LOCKING MECHANISMS:DOUBLE CYLINDER DEAD BOLTS OR OTHER LOCKS THAT PREVENT RAPID EGRESS ARE PROHIBITED. REGISTRATION OF RESIDENTIAL RENTAL PROPERTY. WORK WITHOUT PERMITS.

Case Violations

Case Number: T03DV00360
Case Status: REFERRED
Case Description: RES: MINIMUM HOUSING
Total Violations: 1
Violation Date Code Statue
05/05/2003 CONTACTED BY PHONE

Outstanding Inspections

Case Number: T03DV00360
Case Status: REFERRED
Case Description: RES: MINIMUM HOUSING
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
04/30/2003 INSP - INITIAL CODE ENFORCMENT JHURD Correction Required 4/18/03, VISITED SITE, TOOK PICTURES, MET WITH RESIDENT FELICE, SHE HAD SHOWED ME WHERE HOT WATER TANK WAS LEAKING ON TO FLOOR, HAD A PAN AND A RAG TRYING TO HELP CATCH WATER, DRAIN LINE HAS SMALL HOLE AND SPRAYING WATER, ALSO TPR VALVE IS LEAKING OUTSIDE CONSTANTLY, SMOKE DETECTOR DOES NOT OPERATE, GAVE RESIDENT A SMOKE DETECTOR TO INSTALL, DID SO BEFORE I LEFT, UNIT HAS THREE PRONG OUTLETS AND SHOWS OPEN GROUNDS THROUGH OUT UNIT, ALSO REFRIGERATOR IS PLUGED INTO GFCI OUTLET, OPEN AND EXPOSED ELECTRICAL JUNCTION BOX IN CLOSET, NO GFCI'S IN BATHROOM OR KITCHEN, MARLITE IN BATH ROOM IS PEELING AWAY FROM WALLS AND IS HELD TOGETHER BY DUCT TAPE, WASHING MACHINE HAS NO STAND PIPE FOR DRAINAGE IS CONNECTED STRAIGHT TO CLEAN OUT, SECURITY SCREEN DOOR IN FRONT HAS DOUBLE KEYED DEAD BOLT INSTALLED,
10/06/2003 INSP - FOLLOW UP CODE ENFORCE JHURD Correction Required 10/3/03, REVISITED SITE, TOOK PICTURES, MET WITH RESIDENT FELICE WHO STATED THAT MR.MITCHELL HAS NOT BEEN BACK TO FINISH THE REPAIRS, REFRIGERATOR IS STILL ON GFCI PROTECTED OUTLET, ALL 3 PRONG CONVENIENCE OUTLETS STILL SHOW OPEN GROUND UNDER TEST, WASHING MACHINE DRAIN LINE NOT PROPERLY CONNECTED TO SANITARY SEWER, HAS DRAIN HOSE STUCK INTO CLEAN OUT IN WALL AND NO STAND PIPE, AND BOTH FRONT AND REAR SECURITY SCREEN DOORS HAS DOUBLED KEYED DEAD BOLTS INSTALLED, NOT IN COMPLIANCE
10/06/2003 INSP - FOLLOW UP CODE ENFORCE JHURD Correction Required 10/6/03, WENT TO COURT AND MR MITCHELL DID NOT SHOW FOR COURT, JUDGE LEAVITT ASK ME ABOUT THE POSTING AND I STATED TO HER THAT YES I POSTED HOUSE ON 9/15/03 JUST AFTER COURT AND ALSO THAT RESIDENT FELICE STATED THAT MR MITCHELL DID COME BY ON WEDNESDAY 9/17/03 AND REMOVED POSTING AND STATED TO FELICE THAT HE WOULD GET IN TOUCH WITH ME, AND THAT THERE IS NOTHING WRONG WITH THE HOUSE, MR MITCHELL HAS NOT MADE ANY CONTACT WITH ME AS OF YET, JUDGE LEAVITT MAXED OUT THE FINE TO 2,500.00 AND REFER TO PROSECUTORS OFFICE DUE TO THE FACT HE HAS NOT SHOWED UP FOR ANY COURT HEARINGS AND THAT HE HAS NOT TRIED TO MAKE ANY CONTACT WITH MYSELF. CASE HAS BEEN REFERED TO PROSECUTORS OFFICE.

Completed Activity Special Conditions

Case Description - RES: MINIMUM HOUSING
Case Number - T03DV00360
Case Status: REFERRED
Total Completed Case Activity Conditions: 5
Date Name
05/07/2003 NOTICE OF VIOLATION ISSUED
12/04/2003 POSTING/PUBLICATION
09/04/2003 COURT HEARING INFO
01/07/2004 CASE IS AT PROSECUTORS OFFICE
06/23/2003 CITATION 06011580 ISSUED TO LARRY W MITCHELL