EMERGENCY CALL: FIRE

Completed Inspections

Case Status: VOID
Case Number: T02VL01990
Case Description: COM: FIRE
Total Completed Inspections - 2
End Date Description Inspector Results Comments
09/03/2002 FOLLOW UP CODE VIOLATION LHANLY Approved AFTER THE FACT EMERGENCY CALL TFD OVER WEEKEND TFD RESPONDED TO COMPLAINT THAT SMOKE WAS COMING OUT OF AIR VENTS. THEY FOUND NO INDICATION OF FIRE AND ASKED THAT DSD TAKE A LOOK AT MECHANICAL EQUIPMENT DURING WEEK. 1.) INVESTIGATION OF AC SYSTEM FOUND ALL WIRING AND FUSHING FOR BLOWERS AND COMPRESSORS IN GOOD SHAPE. 2.) I BELIEVE THAT WHEN WATER HEATER WAS LIT FOR NEW TENANTS THAT THERE MAY HAVE BEEN SOME DUST BURN OFF THAT GOT INTO AIR RETURN FOR AIR CONIDITIONING. 3.) THERE WERE 4 OUTSTANDING CODE VIOLATION WITH MECHANCIAL SYSTEMS. A.) CONDENSATE LINE FOR AC NOT PROPERLY TRAPPED.B.) WATER HEATER PRESSURE RELIEF DISCHARGE PIPE IS TIED INTO PVC CONDENSATE DRAIN. C.) PRESSURE RELIEF DISCHARGE LINE IS UNDERSIZED. D.) PLUG RECEPTACLE FOR FURNACE IS NOT GROUNDED. FOLLOW UP 10/31/02.
05/18/2009 INITIAL CODE VIOLATION DCOX Approved No follow up since 2002. Case closed.

Completed Activity Special Conditions

Case Description - COM: FIRE
Case Number - T02VL01990
Case Status: VOID
Total Completed Case Activity Conditions: 1
Date Name
05/18/2009 VIOLATION CLOSED.