Case: T02VL00671
Case Details
Entered Date:
04/03/2002
Applicant:
WALKER VERNON
Description:
MIN HOUSING:ELECTRICAL
Outstanding Inspections
Case Number: T02VL00671
Case Status: SUSPNDED
Case Description: RES: MINIMUM HOUSING
Total Outstanding Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/16/2002 | INITIAL CODE VIOLATION | HLOPEZ | Correction Required | VISITED SITE, FOUND 220 HOT WATER HEATER WITH EXPOSED ELECTRICAL (NOT IN CONDUIT) 2. NO POWER TO KTICHEN OUTLETS. MAY NEED TO INSTALL GFCI WILL REFER PICTURES TO ELECTRICAL INSPECTOR. 3. ILLEGAL 3 PRONG ADAPTER INSTALLED ON A 2 WIRE SYSTEM (HAZARDOUS ELECTRICAL). 4. 1-3 PRONG OUTLET INSTALLED IN KITCHEN IS ILLEGAL. 5. LACK OF WEATHER PROTECTION FOR ENTRY DOORS. 6. DUPLEX DOES NOT HAVE SEPARATE WATER METERS. TENANT HAS NO CONTROL IF EITHER TENANT IS SHUT OFF, WILL DO RESEARCH ON POSSIBLE ILLEGAL SPLIT OF DUPLEX AND ISSUE NOTICE OF VIOLATION WHEN COMPLETE. |
Completed Inspections
Case Status: SUSPNDED
Case Number: T02VL00671
Case Description: RES: MINIMUM HOUSING
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/10/2002 | FOLLOW UP CODE VIOLATION | HLOPEZ | Approved | TENANTS HAVE MOVED OUT, UNIT IS VACANT. WE NO LONGER HAVE JURISTICTION ON VACANT UNIT. CLOSE CASE. |
Completed Activity Special Conditions
Case Description - RES: MINIMUM HOUSING
Case Number - T02VL00671
Case Status: SUSPNDED
Total Completed Case Activity Conditions: 2
| Date | Name |
| 04/23/2002 | CONTACTED IN PERSON |
| 04/23/2002 | NOTICE AND ORDER ISSUED |