Case: T01VL02060
Case Details
Entered Date:
07/17/2001
Applicant:
CHESTERTON LINDA J
Description:
MIN HOUSING:GAS
Outstanding Inspections
Case Number: T01VL02060
Case Status: CLOSED
Case Description: RES: MINIMUM HOUSING
Total Outstanding Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/18/2001 | INITIAL CODE VIOLATION | RCAMACHO | Correction Required | KITCHEN FAUCET IS LOOSE AND LEAKS. ROOF LEAK AT LIGHT FIXTURE. GARBAGE DISPOSAL DOES NOT OPERATE PROPERLY. STOVE HAS BEEN SERVICED BY SOUTHWEST GAS APPROX. 2 WEEKS AGO. EXPOSED WIRING IN WASHROOM MUST BE PROPERLY COVERED. NEED TO CHECK WASHING MACHINE VENT FOR CLOGS. VARIOUS CONVENIECE OUTLETS HAVE NO POWER. MASTER BEDROOM CEILING LEAKS IN CLOSET EXPOSED WIRING MUST BE COVERED PROPERLY. SHEETROCK MUST BE REPLACED. CARPET MUST BE PROPERLY EXTRACTED AND DRIED AND DISENFECTED. BEDROOM 2 HAS EXPOSED WIRING IN CLOSET MUST BE PROPERLY COVERED. TOILET NEEDS TO BE PROPERLY SECURED. BATH TUB BASE NEEDS TO BE PATCHED. GFCI OUTLET NEEDS OVER SINK IN BATHROOM. LIGHT FIXTURE IS NOT OF APPROVED TYPE. COOLER CONNECTION TO FLOAT LEAKS THEREFORE THERE IS NO CONTROL TO SHUT OFF WATER. COOLER HAS NOT BEEN MAINTAINED PROPERLY. |
Completed Inspections
Case Status: CLOSED
Case Number: T01VL02060
Case Description: RES: MINIMUM HOUSING
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/20/2001 | FOLLOW UP CODE VIOLATION | RCAMACHO | Approved | REPAIRS BEING DONE THROUGH CCD OF CITY OF TUCSON. CONTRACTOR ON SITE DOING ALL REPAIRS. CLOSE CASE. |