Case Details

Status:

Closed - Resolved

Type:

RMIN / High Priority / No Air (Swamp Cooler) past 15 days
Address:

Entered Date:

09/26/2023

Applicant:

N/A

Description:

Completed Inspections

Case Status: Closed - Resolved
Case Number: CE-VIO0923-05760
Case Description: RMIN / High Priority / No Air (Swamp Cooler) past 15 days
Total Completed Inspections - 2
End Date Description Inspector Results Comments
10/20/2023 COT - ENFC - Code Enforcement - Follow Up Passed Met with the tenant and the pads have been changed, the pump replaced and all is working. The tenant has no other complaints and will be closing the case at this time. Violation Abated, Close Case. RV.
09/27/2023 COT - ENFC - Code Enforcement - Initial Passed The cooler was running and not cooling. Did go on the roof and the pads have not been changed for some time. Was finally able to remove one of the pads and the pump was not running. Did tap on the pump and the pump started to work and the water started to run. Did find a person working for the owner on the property cleaning one of the unit and he was the one pulling on the pads to remove. Did tell the tenant that the cooler pump was not working and now is pumping water to the pads. The cooler will start to cool once the pads are all wet. Will do N.O.V. on pads being changed. RV.