Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: CE-VIO0824-03418
Case Details
Status:
Active
Type:
RMIN / BLDG 18 - Unit 2207 / Water in kitchen sink shoot water, roach infestation, lights in restroom don't work,
Address:
Entered Date:
08/23/2024
Applicant:
N/A
Description:
Completed Inspections
Case Status: Active
Case Number: CE-VIO0824-03418
Case Description: RMIN / BLDG 18 - Unit 2207 / Water in kitchen sink shoot water, roach infestation, lights in restroom don't work,
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/03/2024 | COT - ENFC - Code Enforcement - Initial | In Violation | 209 PM - Water in kitchen sink leaks out of and shoots water out of faucet, is leaking under sink in cabinet. Roaches in kitchen area. Door in southwest bedroom handle is inoperable. Light bulb was out, I did replace bulb and it works as intended. Toilet in this bathroom is running and does not stop. Outlet in southeast bathroom intermittently tests with open neutral. Outlet in kitchen above dishwasher is loose in wall, recommend changing to a GFCI outlet. -VM |