Case: CE-VIO0726-03176
Case Details
Status:
Closed - Administrative
Type:
RMIN/ Evaporative cooling system does not meet the code for habitable spaces to be maintained at 86 degrees or less.
Address:
Entered Date:
07/29/2026
Applicant:
N/A
Description:
Completed Inspections
Case Status: Closed - Administrative
Case Number: CE-VIO0726-03176
Case Description: RMIN/ Evaporative cooling system does not meet the code for habitable spaces to be maintained at 86 degrees or less.
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/29/2026 | COT - ENFC - Code Enforcement - Initial | In Violation | A site inspection of the subject property was conducted. It was observed that temperatures in several of that habitable spaces in the rental residence were above the allowed 86 degrees for an evaporative cooler. Temperatures coming from the vents averaged 84 degrees; however, some of the rooms temperatures were between 87 and 89 degrees. Temperature checks were conducted between 1:15 PM and 1:45 PM. |