High Priority / RMIN / Unit 29 / No electricity into unit for the last 2 days, extension cords running out of unit to use and to keep refrigerator plugged.
Address:

Entered Date:

03/25/2025

Applicant:

N/A

Description:

Completed Inspections

Case Status: Active
Case Number: CE-VIO0325-01258
Case Description: High Priority / RMIN / Unit 29 / No electricity into unit for the last 2 days, extension cords running out of unit to use and to keep refrigerator plugged.
Total Completed Inspections - 1
End Date Description Inspector Results Comments
03/25/2025 COT - ENFC - Code Enforcement - Initial In Violation Visited the site to assist the case inspectors. Found the electrical new service in violation. Line and load conductors in the same raceways and across meter section(230.7). No bonding(250.92). No grounding electrode system(250..50).

Documents

File Name Document Type  
TC_02356.JPG DOCUMENTS VIEW
TC_02357.JPG DOCUMENTS VIEW
TC_02358.JPG DOCUMENTS VIEW
TC_02359.JPG DOCUMENTS VIEW
TC_02360.JPG DOCUMENTS VIEW
TC_02361.JPG DOCUMENTS VIEW
TC_02362.JPG DOCUMENTS VIEW
TC_02363.JPG DOCUMENTS VIEW
TC_02364.JPG DOCUMENTS VIEW
TC_02365.JPG DOCUMENTS VIEW
TC_02366.JPG DOCUMENTS VIEW
TC_02367.JPG DOCUMENTS VIEW
TC_02368.JPG DOCUMENTS VIEW
TC_02369.JPG DOCUMENTS VIEW
TC_02370.JPG DOCUMENTS VIEW
TC_02371.JPG DOCUMENTS VIEW
TC_02372.JPG DOCUMENTS VIEW
TC_02373.JPG DOCUMENTS VIEW
TC_02374.JPG DOCUMENTS VIEW
TC_02375.JPG DOCUMENTS VIEW
TC_02376.JPG DOCUMENTS VIEW
TC_02377.JPG DOCUMENTS VIEW
TC_02378.JPG DOCUMENTS VIEW
TC_02384.JPG DOCUMENTS VIEW